5.2.16 Digital (Contact) Inputs

 

 

 

P51

 

Select P51 to configure Digital 1 Input Function

Digital Input 1 is a contact closure digital input. It may be operated from external switches or relays and is generally edge triggered on contact closure.

The input may be used to perform a number of functions as selected from the list below.

An open input is detected if the impedance between the terminals is greater than 500 ohms.

A closed input is detected if the impedance between the terminals is less than 200 ohms.

Digital Input 1 is optionally available in all models.

nonE

Input not used (factory default)

Ac.AL

Close the contact to acknowledge any active alarm

SP.SL

Setpoint select.

Close the contact to select setpoint 2.

Open the contact to select setpoint 1.

Loc.b

Keylock. Close the contact to lock the front panel buttons.

Open the contact to unlock the front panel buttons.

t.reS

Timer reset.

Close the contact to reset a currently running timer sequence.

t.rUn

Timer run.

Close the contact to start a timer sequence running.

t.rrS

Timer run/reset.

Close the contact to run a timer sequence.

Open the contact to reset the timer.

t.HLd

Timer hold.

Close the contact to stop the timer at its current time.

Nan

Select manual.

If the controller is in Auto, make the contact permanently to select Manual. If the controller is already in Manual, make then break the contact to return to Auto.

Sby

Standby mode. In this mode control outputs go to zero demand.

 

P52

Select P52 to configure Digital 2 Input Function

Digital input 2 allows the same functions as listed for Digital Input 1 to be performed. Digital Input 2 is not available in 816 but it is optionally available in models 808 and 804.

Digital input 2 is generally edge triggered on contact closure.

nonE

Input not used (factory default)

Ac.AL

Close the contact to acknowledge any active alarm

SP.SL

Setpoint select.

Close the contact to select setpoint 2.

Open the contact to select setpoint 1.

Loc.b

Keylock. Close the contact to lock the front panel buttons.

Open the contact to unlock the front panel buttons.

t.reS

Timer reset.

Close the contact to reset a currently running timer sequence

t.rUn

Timer run.

Close the contact to start a timer sequence running.

t.rrS

Timer run/reset.

Close the contact to run a timer sequence.

Open the contact to reset the timer.

t.HLd

Timer hold.

Close the contact to stop the timer at its current time.

Nan

Select manual.

If the controller is in Auto, make the contact permanently to select Manual. If the controller is already in Manual, make then break the contact to return to Auto.

Sby

Standby mode. In this mode control outputs go to zero demand.